The article discusses the issue of measuring and assessing the features of power line tower earthings using fast-changing waveform. The study analyses the effect of impulse front time and the line span length on errors made during these measurements using impulse meters. It has been found that the assessment conditions similar to the static measurement results occur for the use of 4 μs current impulses and such procedure is useful for evaluating power line tower earthings.
Authors
Additional information
- DOI
- Digital Object Identifier link open in new tab 10.15199/48.2016.02.32
- Category
- Publikacja w czasopiśmie
- Type
- artykuły w czasopismach recenzowanych i innych wydawnictwach ciągłych
- Language
- angielski
- Publication year
- 2016