Resonance problems in UHV transmission lines

The paper presents resonance phenomena observed in 400 kV transmission lines in the Polish power system. Two events are analysed, when shunt reactors used for reactive power compensation, caused overvoltages and overcurrent protection tripping as a result of resonance. An oscillographic fault recordings from protection devices are compared to time domain simulation results. The obtained simulation results match fault recordings, which allows the cause of the observed disturbances to be explained. The paper indicates resonance risks which should be avoided to ensure safe power system operation.