This article presents detailed two-phase diabatic pressure drop data for refrigerant R134a at a saturation pressure of 5.5 bar corresponding to the saturation temperature of 19.4 °C. Study cases have been set for a mass flux varying from 100 to 500 kg m−2 s−1. The obtained data are used as a validation of the void fraction literature models, a set of graphs shows comparisons, for a representative set of experimental conditions, of the two-phase frictional pressure gradients for the adiabatic and diabatic flow. Verification of the acceleration pressure drop predictions for two-phase adiabatic flow showed that all correlations predict that over 60% of experimental data fit in the range of ±30%. The model proposed in this article predicts 63% of presented data within 10% error, and 96% of the data are predicted within 30% error.
Authors
Additional information
- DOI
- Digital Object Identifier link open in new tab 10.1016/j.ijrefrig.2017.05.029
- Category
- Publikacja w czasopiśmie
- Type
- artykuł w czasopiśmie wyróżnionym w JCR
- Language
- angielski
- Publication year
- 2017