Publications Repository - Gdańsk University of Technology

Page settings

polski
Publications Repository
Gdańsk University of Technology

Treść strony

The influence of the motor filtrers on harmonic current emmision in the pro-ective connection of drive systems.

This paper contains detailed analysis of currents in protective wire in engine supplied from frequency converter without any external filters added. It was found that the peak value of current in protective conductor of engine was about 1500 mA at frequencies 5 Hz – 50 Hz. In the continuation of research the dU/dt type motor filter and the sinusoidal filter were tested. It was found that the current in protective wire decreased when the high value of current in protective wire of engine filter appeared. In connection with above in design phase of earthing system for propulsion systems we should consider separation between engine earthing and engine filter. Those solutions strongly reduce level of disturbing currents which derive from filters in neutral connections system from different receiver sets, simultaneously limiting the short-lived touch voltage.

Authors

Additional information

Category
Aktywność konferencyjna
Type
publikacja w wydawnictwie zbiorowym recenzowanym (także w materiałach konferencyjnych)
Language
angielski
Publication year
2003

Source: MOSTWiedzy.pl - publication "The influence of the motor filtrers on harmonic current emmision in the pro-ective connection of drive systems." link open in new tab

Portal MOST Wiedzy link open in new tab