This paper presents the method for determination of leakage inductances of single-phase and multi-winding transformer. The matrix of leakage inductances takes into account leakage self and also leakage mutual magnetic couplings. It is assumed that there is a flux common to all windings and several leakage fluxes referred to a particular winding. The flux linkages of each coil needed fo calculation of leakage inductances was computed by FEM commercial software Opera 3D. The values of leakage inductances matrix have been calculated for special reduced scale traction, 19,3 kVA transformer
Autorzy
Informacje dodatkowe
- Kategoria
- Publikacja w czasopiśmie
- Typ
- artykuły w czasopismach recenzowanych i innych wydawnictwach ciągłych
- Język
- angielski
- Rok wydania
- 2012