Purpose – The paper aims to discuss problems of power and energy losses in a double-circuit overhead transmission line. It was observed from energymeters’ readings, that in such a line, active power losses can be measured as “negative”. The “negative” active power losses appear when the active power injected to the circuit is lower than the active power received at the circuit end. The purpose of this paper is to explain this phenomenon. Theoretical considerations based on mathematical model of the transmission line of pi-type confirming that effect are presented. Power losses related to series impedance of the line and to shunt admittance are calculated. The theoretical considerations are confirmed by measurements done on the real transmission line.